Date | Status | Code | Description | Ref | Location | Comments |
4/5/2017 | Corrected | Correct Below | * | | Panel. | Will need to verify that 10K breakers are adequate for availble fault current. |
4/5/2017 | Transfer | Correct Below | * | | TI panel feeder breaker. | 1. Tennant must be furnished with a letter detailing procedure for getting to electrical room door. Inspector will need copy of letter. 2. Tennant will need a key to the tower basement electrical room door and will need to demonstrate access at next inspection. |
4/5/2017 | Corrected | Correct Below | * | | Panel. | Label to indicate source of supply. |
4/5/2017 | Corrected | Correct Below | * | | Various above ceiling | Support MC and other cables off grid. |
4/5/2017 | Corrected | Correct Below | * | | Electrical drawings. | Need complete stamped, approved set. |
4/5/2017 | Corrected | Correct Below | * | | Pre-made nail tables with lights and fans. | No apparent listing marks. Will need field evaluation. |
4/5/2017 | Corrected | Correct Below | * | | (2) 1 inch home run conduits above ceiling at back of main salon area. | Cannot have more than (9) current carrying #12 conductors without derating to below 20A breaker. |
4/5/2017 | Corrected | Correct Below | * | | Above ceiling by column, In back of main salon by j-boxes, in back panel room. | Support wires for MC do not extend to grid. |
4/5/2017 | Corrected | Correct Below | * | | Fire alarm ceiling detectors. | Need (2) seismic wires. |
4/5/2017 | Corrected | Correct Below | * | | Hanging lights. | Need (2) seismic wires. |