Inspection #: 449596
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Conditional electrical final approved until 5/8/2017 to resolve issue.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/5/2017CorrectedCorrect Below* Panel.Will need to verify that 10K breakers are adequate for availble fault current.
4/5/2017TransferCorrect Below* TI panel feeder breaker.1. Tennant must be furnished with a letter detailing procedure for getting to electrical room door. Inspector will need copy of letter. 2. Tennant will need a key to the tower basement electrical room door and will need to demonstrate access at next inspection.
4/5/2017CorrectedCorrect Below* Panel.Label to indicate source of supply.
4/5/2017CorrectedCorrect Below* Various above ceilingSupport MC and other cables off grid.
4/5/2017CorrectedCorrect Below* Electrical drawings.Need complete stamped, approved set.
4/5/2017CorrectedCorrect Below* Pre-made nail tables with lights and fans.No apparent listing marks. Will need field evaluation.
4/5/2017CorrectedCorrect Below* (2) 1 inch home run conduits above ceiling at back of main salon area.Cannot have more than (9) current carrying #12 conductors without derating to below 20A breaker.
4/5/2017CorrectedCorrect Below* Above ceiling by column, In back of main salon by j-boxes, in back panel room.Support wires for MC do not extend to grid.
4/5/2017CorrectedCorrect Below* Fire alarm ceiling detectors.Need (2) seismic wires.
4/5/2017CorrectedCorrect Below* Hanging lights.Need (2) seismic wires.