Inspection #: 448185
Inspection Type: Final Fire Inspection
Inspector: T.Furch
Result: CondAppr
Comment: REQUESTED BY LEON 344-2581. PLEASE CALL 30 MINUTES PRIOR TO INSPECTION.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/3/2017 Fire 13Correction(s) #1Please correct the following: Add a directional exit sign in corridor 112/111 intersection. Verify dead end travel limit as appears exceded for corridor 109/110. add a door. Also no storage allowed in the corridor.
7/3/2017 Fire 13Correction(s) #1Please correct the following: Label exterior door of electrical panels P207 & TH207 located in stock room
7/3/2017 Fire 13Correction(s) #1Please correct the following: Hang Fire Extinguishers as shown on plans prior to opening. Replace current tags to expire Aug & Provide a new current tag per plan note.
7/3/2017 Fire 13Correction(s) #1Please correct the following: Complete fire alarm acceptance for co. Agreed to defer for several weeks & include with adjacent suites.
7/3/2017 Fire 13Correction(s) #1Please correct the following: Provide install cert for sprinkler work. Address stock room ceiling pocket @ N/W corner of stock room/hall 112.
7/3/2017 Fire 2CCO approvalFire Final approved for CCOretail area - CCO until Aug 3rd 2017Emergency lights installed per plans but results in insufficient light in S/W by office & N/W corner by sales area 105.