Inspection #: 446029
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: early AM if possible. we are working 5am-11am. please call Andy 30 minutes in advance. 907- Requested by: Cody Tims 9072270050 ctims@megawattelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/9/2017TransferCorrect Below* Combination power / control cord for light box LED lights'Cord has been run in conduit from ground level electric room controller to 2nd floor light box in conduit. Installation not allowed per NEC 400.8. Instructions indicate that any part of the feed to lights in conduit is to use conductors other than cord.
3/9/2017TransferCorrect Below* Deleted bollard lighting.Was a change order submitted?
3/9/2017TransferCorrect Below* Exterior receptacles in planter boxes.Need to be dug out of snow for testing.