Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 444048
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: T-bar grid electrical ceiling rough and electrical final.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/5/2017TransferCorrect Below* Panel.Will need to verify that 10K breakers are adequate for availble fault current.
4/5/2017TransferCorrect Below* TI panel feeder breaker.1. Need to verify access. May involve providing tennant a key to a locked room. Need to verify proper labelling.
4/5/2017TransferCorrect Below* Panel.Label to indicate source of supply.
4/5/2017TransferCorrect Below* Various above ceilingSupport MC and other cables off grid.
4/5/2017TransferCorrect Below* Electrical drawings.Need complete stamped, approved set.
4/5/2017TransferCorrect Below* Pre-made nail tables with lights and fans.No apparent listing marks. Will need field evaluation.
4/5/2017TransferCorrect Below* (2) 1 inch home run conduits above ceiling at back of main salon area.Cannot have more than (9) current carrying #12 conductors without derating to below 20A breaker.
4/5/2017TransferCorrect Below* Above ceiling by column, In back of main salon by j-boxes, in back panel room.Support wires for MC do not extend to grid.
4/5/2017TransferCorrect Below* Fire alarm ceiling detectors.Need (2) seismic wires.
4/5/2017TransferCorrect Below* Hanging lights.Need (2) seismic wires.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter