Inspection #: 443871
Inspection Type: Plumbing Rough
Inspector: R.Larson
Result: Cancel
Comment: Call for door code Requested by: Shane 19073506612

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/8/2017TransferPlumbRgh14CommentsSee Inspectors CommentsDrop ceiling.'12 IMC 602.2.1 Materials within plenums. NOTE: ABS piping within the return air plenum does not meet the flame spread index of not more than 25 and a smoke index of not more than 50.
2/8/2017TransferPlumbRgh14CommentsSee Inspectors Comments Water hammer arrestors required. '12 UPC 609.10 Water Hammer; 609.10.1 Mechanical Devices.