Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 441893
Inspection Type: Plumbing Rough
Inspector: R.Larson
Result: Partial
Comment: Item from inspection #441640 (ABS within a return air plenum) corrected. NOTE to second item (609.10.1, "Where listed mechanical devices are used, the manufacturer's specifications as to location and method of installation shall be followed".

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/8/2017TransferPlumbRgh14CommentsSee Inspectors CommentsDrop ceiling.'12 IMC 602.2.1 Materials within plenums. NOTE: ABS piping within the return air plenum does not meet the flame spread index of not more than 25 and a smoke index of not more than 50.
2/8/2017TransferPlumbRgh14CommentsSee Inspectors Comments Water hammer arrestors required. '12 UPC 609.10 Water Hammer; 609.10.1 Mechanical Devices.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS