Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 441640
Inspection Type: Plumbing Rough
Inspector: R.Larson
Result: Correction
Comment: Air tests and rough piping Approved for DWV and Water except as noted as correction.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/8/2017CorrectedPlumbRgh14CommentsSee Inspectors CommentsDrop ceiling.'12 IMC 602.2.1 Materials within plenums. NOTE: ABS piping within the return air plenum does not meet the flame spread index of not more than 25 and a smoke index of not more than 50.
2/8/2017TransferPlumbRgh14CommentsSee Inspectors Comments Water hammer arrestors required. '12 UPC 609.10 Water Hammer; 609.10.1 Mechanical Devices.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter