Click Here To View Another Inspection Inspection #: 439621 Inspection Type: Refrigeration Rough Inspector: Y.Dovba Result: Approved Comment: Refrigeration piping rough-in and tests Approved, per plans 4-line-sets supply & return piping @ 325 & 350psig including Variable Flow System along with distribution box in mechanical room 1st floor. NOTE 1) types & amounts of refrigerant will be required at final on company letter head. NOTE 2) condensate drains on 4-AC & Heating units in entry ways will be inspected at final. Inspection Corrections DateStatusCodeDescriptionRefLocationComments