Inspection #: 437035
Inspection Type: Final Fire Inspection
Inspector: T.Furch
Result: Correction
Comment: Please call 30 min prior to inspection. Thank you. Requested by: David Kim 748-2137 northlanddevelopment@gmail.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/5/2017 Fire 13Correction(s) #1Please correct the following:hood fryer applianceVerify the required clearance between the fryer and the side wall. Curently there is zero clearance. Show either the code section, appliance listing, etc allowing this. Verbal approval by previous inspector/inspection not valid unless in writing.
1/5/2017 Fire 13Correction(s) #1Please correct the following:Pho VietnamInstall did not match approved plans. angled wall squared off and door added. Provide a change order for wall, door thumbturn hardware & sink blocking door.
1/5/2017 Fire 13Correction(s) #1Please correct the following:Pho Vietnam hoodadd a baffel between the stove and fryer. remove duct tape from hood intake vent.