Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 436624
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: TI electrical final approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/19/2016CorrectedCorrect Below* Circuit #3 "small cooler / freezer receptacles.Freezer FLA is 13.2A. Cooler FLA is 10.6A. 20A circuit is overloaded. Separate circuits required for each appliance. Check freezer receptacle; over 12A rated appliance will require 20A rated device.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter