Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 436453
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Please call 15 minutes prior to inspection. Requested by: Kyle 907-903-8981

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/19/2016TransferCorrect Below* Circuit #3 "small cooler / freezer receptacles.Freezer FLA is 13.2A. Cooler FLA is 10.6A. 20A circuit is overloaded. Separate circuits required for each appliance. Check freezer receptacle; over 12A rated appliance will require 20A rated device.
12/16/2016CorrectedCorrect Below* Sign circuit20A dedicated circuit required per 600.5(A).
12/16/2016CorrectedCorrect Below* Point of sale counter.Recptacles within 6 feet of sink require GFCI protection. See 210. 8(B)(5). Some "readily accessible" issues.
12/16/2016CorrectedCorrect Below* Kitchen 120V 15A and 20A receptacles.All need GFCI protection. See 210.8(b)(2). Some locations will have "readily accessible" issues. See article 100 Definitions.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter