Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 436299
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: TI electrical final and reinspect of ceiling rough corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/16/2016TransferCorrect Below* Sign circuit20A dedicated circuit required per 600.5(A).
12/16/2016TransferCorrect Below* Point of sale counter.Recptacles within 6 feet of sink require GFCI protection. See 210. 8(B)(5). Some "readily accessible" issues.
12/16/2016TransferCorrect Below* Kitchen 120V 15A and 20A receptacles.All need GFCI protection. See 210.8(b)(2). Some locations will have "readily accessible" issues. See article 100 Definitions.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter