Date | Status | Code | Description | Ref | Location | Comments |
12/7/2016 | | EF1 | Correct Below | | Rooftop unit | Labelling on unit requires 90A breaker. |
12/7/2016 | | EF1 | Correct Below | | Access to feeder / service disconnect. | Tennant must be provided with a key to the electrical room. |
12/7/2016 | | EF1 | Correct Below | | Rooftop unit. | New rooftop unit fed using existing circuit does not have a legal ground fault current path per 250.118(6) due to liquid tight flex. Circuit needs an EGC. |
12/6/2016 | | EF1 | Correct Below | | Restroom water heater. | Breaker lock needs to meet NEC 110.25 or needs disconnect within sight. |
12/6/2016 | | EF1 | Correct Below | | Stock room. | Emergency light above door not coming on when light circuit turned off. |
12/6/2016 | | EF1 | Correct Below | | Panel | Need to label as to source of supply per NEC 408.4(B). Needs to show panel or service from which circuit originates. Needs to show electric room designation. |
12/6/2016 | | EF1 | Correct Below | | Rooftop unit. | Need to inspect for proper OCPD, disconnect, working clearances, service receptacle, etc. |
12/2/2016 | | EF1 | Correct Below | | in front soffit - receptacles must be supported by top and bottom screws, MC connector not properly connected to light | |
12/2/2016 | | EF1 | Correct Below | | provide access to flex connector under back POS cabinets | |
12/2/2016 | | EF1 | Correct Below | | dead receptacle in bathroom | |
12/2/2016 | | EF1 | Correct Below | | lockable disconnect required for water heater in bathroom | |
12/2/2016 | | EF1 | Correct Below | | exit lights dead, must be on lighting sircuit in the room where the sign is located | |
12/2/2016 | | EF1 | Correct Below | | emergency lights in stockroom must be on same lighting circuit as the normal lights in that room | |
12/2/2016 | | EF1 | Correct Below | | em light dead in short hallway | |
12/2/2016 | | EF1 | Correct Below | | need to inspect receptacle behind dressing room mirror or see connections | |
12/2/2016 | | EF1 | Correct Below | | still need to inspect rooftop unit, feeder disconnect location and verify labeling on panel | |