Inspection #: 435422
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: TI electrical final approved. Tennant has been provided with a key to the electrical room.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/7/2016 EF1Correct Below Rooftop unitLabelling on unit requires 90A breaker.
12/7/2016 EF1Correct Below Access to feeder / service disconnect.Tennant must be provided with a key to the electrical room.
12/7/2016 EF1Correct Below Rooftop unit.New rooftop unit fed using existing circuit does not have a legal ground fault current path per 250.118(6) due to liquid tight flex. Circuit needs an EGC.
12/6/2016 EF1Correct Below Restroom water heater.Breaker lock needs to meet NEC 110.25 or needs disconnect within sight.
12/6/2016 EF1Correct Below Stock room.Emergency light above door not coming on when light circuit turned off.
12/6/2016 EF1Correct Below PanelNeed to label as to source of supply per NEC 408.4(B). Needs to show panel or service from which circuit originates. Needs to show electric room designation.
12/6/2016 EF1Correct Below Rooftop unit.Need to inspect for proper OCPD, disconnect, working clearances, service receptacle, etc.
12/2/2016 EF1Correct Below in front soffit - receptacles must be supported by top and bottom screws, MC connector not properly connected to light 
12/2/2016 EF1Correct Below provide access to flex connector under back POS cabinets 
12/2/2016 EF1Correct Below dead receptacle in bathroom 
12/2/2016 EF1Correct Below lockable disconnect required for water heater in bathroom 
12/2/2016 EF1Correct Below exit lights dead, must be on lighting sircuit in the room where the sign is located 
12/2/2016 EF1Correct Below emergency lights in stockroom must be on same lighting circuit as the normal lights in that room 
12/2/2016 EF1Correct Below em light dead in short hallway 
12/2/2016 EF1Correct Below need to inspect receptacle behind dressing room mirror or see connections 
12/2/2016 EF1Correct Below still need to inspect rooftop unit, feeder disconnect location and verify labeling on panel 