Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 435337
Inspection Type: Final Electrical
Inspector: H8
Result: Correction
Comment: Requested by: M.Green ||

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/6/2016TransferEF1Correct Below Restroom water heater.Breaker lock needs to meet NEC 110.25 or needs disconnect within sight.
12/6/2016TransferEF1Correct Below Rooftop unit.Need to inspect for proper OCPD, disconnect, working clearances, service receptacle, etc.
12/6/2016TransferEF1Correct Below PanelNeed to label as to source of supply per NEC 408.4(B). Needs to show panel or service from which circuit originates. Needs to show electric room designation.
12/6/2016TransferEF1Correct Below Stock room.Emergency light above door not coming on when light circuit turned off.
12/2/2016TransferEF1Correct Below in front soffit - receptacles must be supported by top and bottom screws, MC connector not properly connected to light 
12/2/2016TransferEF1Correct Below provide access to flex connector under back POS cabinets 
12/2/2016TransferEF1Correct Below dead receptacle in bathroom 
12/2/2016TransferEF1Correct Below lockable disconnect required for water heater in bathroom 
12/2/2016TransferEF1Correct Below exit lights dead, must be on lighting sircuit in the room where the sign is located 
12/2/2016TransferEF1Correct Below emergency lights in stockroom must be on same lighting circuit as the normal lights in that room 
12/2/2016TransferEF1Correct Below em light dead in short hallway 
12/2/2016TransferEF1Correct Below need to inspect receptacle behind dressing room mirror or see connections 
12/2/2016TransferEF1Correct Below still need to inspect rooftop unit, feeder disconnect location and verify labeling on panel 
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter