Inspection #: 435106
Inspection Type: Final Electrical
Inspector: H8
Result: Cancel
Comment: Requested by: Kyle 907-903-8981 ||

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/2/2016TransferEF1Correct Below in front soffit - receptacles must be supported by top and bottom screws, MC connector not properly connected to light 
12/2/2016TransferEF1Correct Below provide access to flex connector under back POS cabinets 
12/2/2016TransferEF1Correct Below dead receptacle in bathroom 
12/2/2016TransferEF1Correct Below lockable disconnect required for water heater in bathroom 
12/2/2016TransferEF1Correct Below exit lights dead, must be on lighting sircuit in the room where the sign is located 
12/2/2016TransferEF1Correct Below emergency lights in stockroom must be on same lighting circuit as the normal lights in that room 
12/2/2016TransferEF1Correct Below em light dead in short hallway 
12/2/2016TransferEF1Correct Below need to inspect receptacle behind dressing room mirror or see connections 
12/2/2016TransferEF1Correct Below still need to inspect rooftop unit, feeder disconnect location and verify labeling on panel 