Date | Status | Code | Description | Ref | Location | Comments |
12/2/2016 | Transfer | EF1 | Correct Below | | emergency lights in stockroom must be on same lighting circuit as the normal lights in that room | |
12/2/2016 | Transfer | EF1 | Correct Below | | em light dead in short hallway | |
12/2/2016 | Transfer | EF1 | Correct Below | | need to inspect receptacle behind dressing room mirror or see connections | |
12/2/2016 | Transfer | EF1 | Correct Below | | still need to inspect rooftop unit, feeder disconnect location and verify labeling on panel | |
12/2/2016 | Transfer | EF1 | Correct Below | | in front soffit - receptacles must be supported by top and bottom screws, MC connector not properly connected to light | |
12/2/2016 | Transfer | EF1 | Correct Below | | provide access to flex connector under back POS cabinets | |
12/2/2016 | Transfer | EF1 | Correct Below | | lockable disconnect required for water heater in bathroom | |
12/2/2016 | Transfer | EF1 | Correct Below | | exit lights dead, must be on lighting sircuit in the room where the sign is located | |