Date | Status | Code | Description | Ref | Location | Comments |
11/30/2016 | | EF1 | Correct Below | | Sales floor ceiling. | Some lighting track needs extra seismic wires. Approx every 4 ft. At least (1) EM light needs seismic wire. |
11/30/2016 | | EF1 | Correct Below | | Dresing room southwest. | Chandalier box needs (2) large KO seals. |
11/30/2016 | | EF1 | Correct Below | | Wall cabinets behind POS cabinets. | Dead receptacle. |
11/30/2016 | | EF1 | Correct Below | | Under POS counter cabinets. | At least (1) 4sq j-box not accessible. |
11/30/2016 | | EF1 | Correct Below | | Stock room | Several receptacles dead. |
11/30/2016 | | EF1 | Correct Below | | Stock room, back room above electrical panels. | (1) EM light completely dead. (1) light has one head not functioning. |
11/30/2016 | | EF1 | Correct Below | | Panels | Label as to source of supply. Will need to verify that tennant breaker in electrical room is labelled . |