Inspection #: 434644
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Approved
Comment: Requested by: kyle 907-903-8981 ||

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/30/2016 EF1Correct Below Sales floor ceiling.Some lighting track needs extra seismic wires. Approx every 4 ft. At least (1) EM light needs seismic wire.
11/30/2016 EF1Correct Below Dresing room southwest.Chandalier box needs (2) large KO seals.
11/30/2016 EF1Correct Below Wall cabinets behind POS cabinets.Dead receptacle.
11/30/2016 EF1Correct Below Under POS counter cabinets.At least (1) 4sq j-box not accessible.
11/30/2016 EF1Correct Below Stock roomSeveral receptacles dead.
11/30/2016 EF1Correct Below Stock room, back room above electrical panels.(1) EM light completely dead. (1) light has one head not functioning.
11/30/2016 EF1Correct Below PanelsLabel as to source of supply. Will need to verify that tennant breaker in electrical room is labelled .