Date | Status | Code | Description | Ref | Location | Comments |
12/2/2016 | | EF1 | Correct Below | | low valtage wiring in ceiling must be supported off the grid, remove all abandoned cabling | |
12/2/2016 | | EF1 | Correct Below | | existing life safety issue at MDP - existing open spaces in MDP must be closed off with breaker blanks | |
12/2/2016 | | ET9 | correct below | | only 2 pieces of equiment rated 208V shown on plans but 4 are onsite - add receptacles and update panel shedule and load calcs | |
12/2/2016 | | EF1 | Correct Below | | in panel - thumb screw lock-in device reequired for egress lighting circuit | |
12/2/2016 | | EF1 | Correct Below | | label breaker supplying this space with tenant space number and new panel numbers - existing breakers must be identified with tenant space number | |
12/2/2016 | | EF1 | Correct Below | | no receptacles provided for xerox 2 copiers (1-color -1 b/w) | |
12/2/2016 | | EF1 | Correct Below | | only two 208V receptacles provided for 3 pieces rated 208/240 | |
12/2/2016 | | EF1 | Correct Below | | more detail required on panel schedule - no two circuits should be labeled alike | |
12/2/2016 | | FE1 | Correct Below | | 40 amp circuit appears too big for titan1264 rated 18 amps. | |
12/2/2016 | | EF1 | Correct Below | | no apparent third party listing (field evaluation required) on the following equipment - Horizon folder, challenge hole punch, gluing machine, identificatin products laminator (2) | |