Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 434221
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Approved
Comment: unlisted equipment removed

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/2/2016 EF1Correct Below low valtage wiring in ceiling must be supported off the grid, remove all abandoned cabling 
12/2/2016 EF1Correct Below existing life safety issue at MDP - existing open spaces in MDP must be closed off with breaker blanks 
12/2/2016 ET9correct below only 2 pieces of equiment rated 208V shown on plans but 4 are onsite - add receptacles and update panel shedule and load calcs 
12/2/2016 EF1Correct Below in panel - thumb screw lock-in device reequired for egress lighting circuit 
12/2/2016 EF1Correct Below label breaker supplying this space with tenant space number and new panel numbers - existing breakers must be identified with tenant space number 
12/2/2016 EF1Correct Below no receptacles provided for xerox 2 copiers (1-color -1 b/w) 
12/2/2016 EF1Correct Below only two 208V receptacles provided for 3 pieces rated 208/240 
12/2/2016 EF1Correct Below more detail required on panel schedule - no two circuits should be labeled alike 
12/2/2016 FE1Correct Below 40 amp circuit appears too big for titan1264 rated 18 amps. 
12/2/2016 EF1Correct Below no apparent third party listing (field evaluation required) on the following equipment - Horizon folder, challenge hole punch, gluing machine, identificatin products laminator (2) 
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter