Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 433250
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Correction
Comment: Inspector is Mike Green 317-6980. Strongly suggest getting licensed electrical contractor to do this work.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/30/2017Transfer01See inspection comments Under mobile home.Support, fasten MC cable off of ground to trailer frame.
6/30/2017Transfer01See inspection comments Exterior receptacles.Verify GFCI protection. If replacing receptacle(s) will need to be weather resistant and tamper resistant type with "extra duty" weatherproof cover.
6/30/2017Transfer01See inspection comments Headbolt heater receptacle.Receptacle needed by parking area for plugging-in car engine block heaters. Needs dedicated circuit. Needs "extra-duty" weatherproof cover. Needs GFCI protection. Receptacle will need to be tamper resistant and weather resistant type.
6/30/2017Transfer01See inspection comments Jacuzzi tub.Needs GFCI breakers for motor and heater. Needs 16 inch by 16 inch access panel. Receptacles need to face access.
6/30/2017Transfer01See inspection comments Kitchen conuntertop.Receptacles need GFCI protection.
6/30/2017Transfer01See inspection comments Panel.Needs deadfront and cover that fits that enclosure, panel schedule.
6/30/2017Transfer01See inspection comments Feeder J-box under mobile home.Needs ground wire connections.
6/30/2017Transfer01See inspection comments Water line and gas line under trailer.Needs #6 copper grounding electrode conductor from panel. Do not run through metal conduit. Cannot be spliced.
6/30/2017Transfer01See inspection comments 3-wire feeder from service.Mobile home is more than 30 feet from service. Needs post mounted disconnect at the trailer space. Also requires the following: *Treated wood for post. *Disconnect needs to be labelled "suitable for use as service equipment". *(2) ground rods needed at post mounted disconnect. *Connect ground rods to disconnect with #6 copper wire. *Bond neutral to ground at disconnect. *Feeder from post mounted disconnect into mobile home needs to include a #6 copper ground wire. *Feeder underground from post mounted disconnect to trailer will need to be burried 24 inches deep and inspected before cover. *Coreflow will need to cover feeders completely where above ground under mobile home.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS