Inspection #: 430020
Inspection Type: Electrical Inspection
Inspector: H8
Result: Partial
Comment: electrical rough-in approved tag #33661

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/21/2016TransferViolation Below* Junction boxes undersized for amount of cables spliced. Additional boxes may be req'd. (4-11/16 inch deep bracketed) 
10/21/2016TransferViolation Below* #12 awg wire req'd for 20 amp ckt. (yellow). 
10/21/2016TransferViolation Below* Properly ground metal boxes. 
10/21/2016TransferViolation Below* fasten cable within 12" of box. 
10/21/2016TransferViolation Below* Ensure ckts are reconnected to proper breaker. 
10/21/2016TransferViolation Below* Orientate junction boxes to be accessible after siding is installed. 
10/21/2016TransferViolation Below* Call for reinspect when corrections are made. 
10/21/2016TransferViolation Below* may be additional corrections. 