Inspection #: 429686
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Approved
Comment: corrections made electrical final approved

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/18/2016 Correct Below* Secure receptacle under cash drop cabinets. 
10/18/2016 Correct Below* Isolated ground receptacles installed in cash drop area. Currently not wired as isolated ground. 
10/18/2016 Correct Below* Provide information for UL listing for display cases. 
10/18/2016 Correct Below* Small specialty lighting does not appear to be UL listed. 
10/18/2016 Correct Below* Dream Steamer not unpackaged or installed. 
10/18/2016 Correct Below* Storage room above ceiling. Open j-boxes, and j-boxes not supported. Conduit req'd to be supported within 3' of box. 
10/18/2016 Correct Below* MDP. Post floor plan to correspond with panel schedule. 
10/18/2016 Correct Below* Other closet or storage spaces req'd to meet local amendment 23.30.410.17. Fluorescent req'd to be totally enclosed. 
10/18/2016 Correct Below* GFCI protection for all receptacles in Commercial Kitchen.Area has a sink and permanent provisions for food prep and cooking.