Inspection #: 429389
Inspection Type: Final Electrical
Inspector: V.Fosberg
Result: Approved
Comment: electrical final for second phase and first phase approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/14/2016CorrectedCorrect Below* EM ltg req'd to comply with 700.12 (F) for kitchen area. For restaurant area, Same code section, Exception No. 1. 
9/9/2016CorrectedCorrect Below* 120 volt 15 and 20 amp receptacles req'd to be GFCI protected. (Near walk in cooler). 
9/9/2016CorrectedCorrect Below* Provide name plate info for walk in cooler condensor to verify voltage and overcurrent protection 
9/9/2016CorrectedCorrect Below* Kitchen grill wall receptacles req'd to be GFCI protected. 
9/9/2016CorrectedCorrect Below* 20 amp overcurrent protection for ice maker near panel. 
9/9/2016CorrectedCorrect Below* Plastic bushing at terminations where conduit contains #4 awg or larger conductor. (panel and dishwasher). 
9/9/2016CorrectedCorrect Below* Provide stamped drawings. 
9/9/2016CorrectedCorrect Below* 20 amp overcurrent protection for coffee pot receptacle in restaurant area. 
9/9/2016CorrectedCorrect Below* Verify if receptacle behind beer cooler is accessible. Does not appear to be. If within 6' of sink req'd to be GFCI protected. 
8/8/2016CorrectedCorrect Item Below* Seating area above drop ceilingProperly support existing communications/tv boxes and associated conduits.