Click Here To View Another Inspection Inspection #: 427575 Inspection Type: Ceiling / Act Inspector: H8 Result: Correction Comment: 1) WIRES SHALL NOT BE MORE THAN 1" IN 6" OUT OF PLUMB. 2) WIRES THAT SUPPORT GRID CEILINGS SHALL NOT SUPPORT ANY OTHER MATERIAL. 3) WIRES SHALL BE MAX 4' OC THAT SUPPORT MAINS. 4) TEES OVER 8" LONG REQUIRE WIRE SUPPORTS. 5) IDENTIFICATION OF ALL RATED WALLS REQUIRED AT CONCEALED SPACES. 6) COMLETE ALL FIRE STOPPING. Inspection Corrections DateStatusCodeDescriptionRefLocationComments