Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 424330
Inspection Type: Final Electrical
Inspector: H8
Result: Partial
Comment: conditional Electrical final until 11/30/2016

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/14/2016TransferEF1Correct Below phase 2 not completed yet 
10/14/2016TransferEF1Correct Below identify em light in kitchen on battery back-up 
10/14/2016TransferCorrect Below* EM ltg req'd to comply with 700.12 (F) for kitchen area. For restaurant area, Same code section, Exception No. 1. 
9/9/2016TransferCorrect Below* Verify if receptacle behind beer cooler is accessible. Does not appear to be. If within 6' of sink req'd to be GFCI protected. 
9/9/2016TransferCorrect Below* 120 volt 15 and 20 amp receptacles req'd to be GFCI protected. (Near walk in cooler). 
9/9/2016TransferCorrect Below* Provide name plate info for walk in cooler condensor to verify voltage and overcurrent protection 
9/9/2016TransferCorrect Below* Kitchen grill wall receptacles req'd to be GFCI protected. 
9/9/2016TransferCorrect Below* 20 amp overcurrent protection for ice maker near panel. 
9/9/2016TransferCorrect Below* Plastic bushing at terminations where conduit contains #4 awg or larger conductor. (panel and dishwasher). 
9/9/2016TransferCorrect Below* Provide stamped drawings. 
9/9/2016TransferCorrect Below* 20 amp overcurrent protection for coffee pot receptacle in restaurant area. 
8/8/2016TransferCorrect Item Below* Seating area above drop ceilingProperly support existing communications/tv boxes and associated conduits.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS