| Date | Status | Code | Description | Ref | Location | Comments |
| 10/14/2016 | Transfer | EF1 | Correct Below | | phase 2 not completed yet | |
| 10/14/2016 | Transfer | EF1 | Correct Below | | identify em light in kitchen on battery back-up | |
| 10/14/2016 | Transfer | Correct Below | * | | EM ltg req'd to comply with 700.12 (F) for kitchen area. For restaurant area, Same code section, Exception No. 1. | |
| 9/9/2016 | Transfer | Correct Below | * | | Verify if receptacle behind beer cooler is accessible. Does not appear to be. If within 6' of sink req'd to be GFCI protected. | |
| 9/9/2016 | Transfer | Correct Below | * | | 120 volt 15 and 20 amp receptacles req'd to be GFCI protected. (Near walk in cooler). | |
| 9/9/2016 | Transfer | Correct Below | * | | Provide name plate info for walk in cooler condensor to verify voltage and overcurrent protection | |
| 9/9/2016 | Transfer | Correct Below | * | | Kitchen grill wall receptacles req'd to be GFCI protected. | |
| 9/9/2016 | Transfer | Correct Below | * | | 20 amp overcurrent protection for ice maker near panel. | |
| 9/9/2016 | Transfer | Correct Below | * | | Plastic bushing at terminations where conduit contains #4 awg or larger conductor. (panel and dishwasher). | |
| 9/9/2016 | Transfer | Correct Below | * | | Provide stamped drawings. | |
| 9/9/2016 | Transfer | Correct Below | * | | 20 amp overcurrent protection for coffee pot receptacle in restaurant area. | |
| 8/8/2016 | Transfer | Correct Item Below | * | | Seating area above drop ceiling | Properly support existing communications/tv boxes and associated conduits. |