| Date | Status | Code | Description | Ref | Location | Comments |
| 2/7/2018 | Transfer | Correct service item below | * | | All exterior receptacles including under trailer. | Need GFCI protection. Receptacles under trailer will need GFCI device to be readily accessible. |
| 2/7/2018 | Transfer | Correct service item below | * | | Type URD feeder conductors under trailer. | Need coreflow or conduit protection. |
| 2/7/2018 | Transfer | Correct service item below | * | | Underground direct burrial feeder conductors. | Need to be 24 inches deep minimum. Conductors in PVC or liquid tight need to be 18 inches deep min. Ridgid or IMC can be 6 inches deep min. |