Inspection #: 423877
Inspection Type: Electrical Service
Inspector: M.Green
Result: Correction
Comment: late pm Elvis 231-5598 Mobile home rough electrical set-up. No green tag at this time. Correct items below and request a reinspection on line.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/7/2018TransferCorrect service item below* All exterior receptacles including under trailer.Need GFCI protection. Receptacles under trailer will need GFCI device to be readily accessible.
2/7/2018TransferCorrect service item below* Type URD feeder conductors under trailer.Need coreflow or conduit protection.
2/7/2018TransferCorrect service item below* Underground direct burrial feeder conductors.Need to be 24 inches deep minimum. Conductors in PVC or liquid tight need to be 18 inches deep min. Ridgid or IMC can be 6 inches deep min.