Inspection #: 423872
Inspection Type: Final Electrical
Inspector: H8
Result: Partial
Comment: Conditional Electrical final approved for Restaurant/bar side of area (phase 1) with exception of EM lighting correction. See correction for restaurant side. Call for reinspect prior to opening to public.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/9/2016TransferCorrect Below* Verify if receptacle behind beer cooler is accessible. Does not appear to be. If within 6' of sink req'd to be GFCI protected. 
9/9/2016TransferCorrect Below* 120 volt 15 and 20 amp receptacles req'd to be GFCI protected. (Near walk in cooler). 
9/9/2016TransferCorrect Below* Provide name plate info for walk in cooler condensor to verify voltage and overcurrent protection 
9/9/2016TransferCorrect Below* Kitchen grill wall receptacles req'd to be GFCI protected. 
9/9/2016TransferCorrect Below* 20 amp overcurrent protection for ice maker near panel. 
9/9/2016TransferCorrect Below* Plastic bushing at terminations where conduit contains #4 awg or larger conductor. (panel and dishwasher). 
9/9/2016TransferCorrect Below* Provide stamped drawings. 
9/9/2016TransferCorrect Below* 20 amp overcurrent protection for coffee pot receptacle in restaurant area. 
8/8/2016TransferCorrect Item Below* Seating area above drop ceilingProperly support existing communications/tv boxes and associated conduits.