Inspection #: 421712
Inspection Type: Electrical Inspection
Inspector: M.Green
Result: Approved
Comment: Upgrade of (2) tennant meters / feeders approved. Kay Jewellers meter tag #32500. Engineer provided AFC info as requested at last inspection. AFC info attached.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/26/2016 Electrical OtherElectrical OtherPlease correct the following:Fused meter /main.Meter / main is on load side of service. Meter / main is labelled as suitable as service equipment only.
8/26/2016 Electrical OtherElectrical OtherPlease correct the following:Meter main.What is the available fault current at this point? Engineer needs to show on drawings.
8/26/2016 Electrical OtherElectrical OtherPlease correct the following:Kay Jewellers branch circuit panel.10K AIC rated equipment installed at this point. What is the available fault current? Only 50 ft from the meter.
8/26/2016 Electrical OtherElectrical OtherPlease correct the following:PanelFeeder conduit needs insuated bushing.
8/26/2016 Electrical OtherElectrical OtherPlease correct the following:PlansNeed to have set with MOA approval stamp showing AFCs as per comments above.