8/26/2016 | | Electrical Other | Electrical Other | Please correct the following: | Fused meter /main. | Meter / main is on load side of service. Meter / main is labelled as suitable as service equipment only. |
8/26/2016 | | Electrical Other | Electrical Other | Please correct the following: | Meter main. | What is the available fault current at this point? Engineer needs to show on drawings. |
8/26/2016 | | Electrical Other | Electrical Other | Please correct the following: | Kay Jewellers branch circuit panel. | 10K AIC rated equipment installed at this point. What is the available fault current? Only 50 ft from the meter. |
8/26/2016 | | Electrical Other | Electrical Other | Please correct the following: | Panel | Feeder conduit needs insuated bushing. |
8/26/2016 | | Electrical Other | Electrical Other | Please correct the following: | Plans | Need to have set with MOA approval stamp showing AFCs as per comments above. |