Inspection #: 415650
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: Corrections made, if possible can this be inspected before 10am? Please call 10 minutes before inspection , thank you Requested by: Kyle 907-903-8981 ||

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/15/2016 EF1Correct Below Point of sale.Receptacles need to be isolated ground type.
7/15/2016 EF1Correct Below Walk in freezer fan coil unit.Needs disconnect.
7/15/2016 EF1Correct Below Roof top condenser unit.Fused disconnect does not have working clearances.
7/15/2016 EF1Correct Below PanelsTrim cannot impeed removal of panel cover.
7/15/2016 EF1Correct Below PanelsLabel as to source of supply per NEC 408.4(B).