Inspection #: 409296
Inspection Type: Ceiling Rough Electrical
Inspector: H8
Result: Correction
Comment: Requested by: Mike Wascom (907) 388-1937 sanderson@encoreak.com ||

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/7/2016Transfercorrection for Ceiling below* VIP Room.Ltg ckt in VIP room (NW corner) overloaded. Plans call for 4 ea. surface mount strip fixtures to be installed. Changed to 20 ea. recessed can type fixtures.