Inspection #: 404128
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Approved
Comment: Requested by: Shawn 870-267-3424 ||

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/27/2016 Correct Below* New light fixtures required to be attached to ceiling grid in approved manner. 
5/27/2016 Correct Below* Above drop ceilingSeismic wire may not have more than 1" of horizontal deflection per every 6" of vertical.
5/27/2016 Correct Below* Above drop ceilingFixture whip may not be more than 6' unsupported.