Inspection Type: Electrical Rough
Inspector: H8
Result: Partial
Comment: Hospital grade MC to IG receptacles replaced with MC IG cable. Electrical wall rough approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/19/2016TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:All isolated ground receptacles.Hospital grade MC cable cannot be used as wiring method. The MC cable sheath cannot be used as the EGC for bonding enclosures.