Inspection #: 399960
Inspection Type: Final Plumbing
Inspector: G.Hile
Result: Approved
Comment: Plumbing Final - Approved Corrections addressed, Plumbing Final approved. OK for CO.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/4/2016 PlumbFinalCommentsSee Inspector Comments Per 2009 UPC section 413.1 ASSE 1070 temp valves require at each public lav (point of use)
4/4/2016 PlumbFinalCommentsSee Inspector Comments Per local amendment section 23.25.508.0-508.4 & approved plans relief discharge piping is required to be piped into a mop sink near-by.
4/4/2016 PlumbFinal6ADA RequirementsFixtures are not installed per ADA requirements-Per ANSI A1171.1 code Per ICC A117.1-2009 ADA section 1003.11.2.4.6 flush controls, hand-operated flush controls shall be located on the open side of the water closet.