Click Here To View Another Inspection Inspection #: 396508 Inspection Type: Final Fire Inspection Inspector: C.Torrey Result: Correction Comment: Requested by: MATT/ SUSIE 262-880-7482/ 262-898-6729Corrections needed for CO:1) Area through the rear exit corridor needs yellow striping on the floor & red lettering on walls stating "Exit corridor - NO storage allowed" (min. 2" high lettering; Include area behind the intervening door which needs to swing fully open; Post 2 "NOT AN EXIT" decals/signs above bathroom door & opening into stockroom. NOTE: Exit corridor through employee area...nearly totally blocked by storage - NOT ALLOWED ever.2) Remove the orange sprinkler cover from head near rear exit door, reinstall missing ceiling tile adjacent to it.3) Relocate the extinguisher & decal above it, blocked by storage in rear employee area, to adjacent to the intervening exit door near dressing rooms as directed on inspection.4) Unit # required outside of rear exit door into corridor & on tile at front entry (# 324 - NOT 214A) as shown on Inspection request form.NOTE: Intervening exit door by dressing rooms, can have "Emergency Exit Only" sign placed on it if desired. Inspection Corrections DateStatusCodeDescriptionRefLocationComments