Inspection #: 389204
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: Engineer is sending field change order for changes to 1-line dwg.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/16/2015 EF1Correct Below PlansEngineer needs to submit field change order OK'ing Lee's Embroidery feeder and Claire's feeder in same conduit. Needs to OK 70A breaker (60A shown). Will verify 22K AIC feeder breaker rating at next visit.
12/16/2015 EF1Correct Below Back room.EM light not coming on in battery mode.
12/16/2015 EF1Correct Below ThroughoutRemove cords, temp lighting from ceiling.
12/16/2015 EF1Correct Below Receptacle by panel.Reverse polarity.
12/16/2015 EF1Correct Below ThroughoutInstall trim plates.