Date | Status | Code | Description | Ref | Location | Comments |
12/16/2015 | | EF1 | Correct Below | | Plans | Engineer needs to submit field change order OK'ing Lee's Embroidery feeder and Claire's feeder in same conduit. Needs to OK 70A breaker (60A shown). Will verify 22K AIC feeder breaker rating at next visit. |
12/16/2015 | | EF1 | Correct Below | | Back room. | EM light not coming on in battery mode. |
12/16/2015 | | EF1 | Correct Below | | Throughout | Remove cords, temp lighting from ceiling. |
12/16/2015 | | EF1 | Correct Below | | Receptacle by panel. | Reverse polarity. |
12/16/2015 | | EF1 | Correct Below | | Throughout | Install trim plates. |