| Date | Status | Code | Description | Ref | Location | Comments |
| 1/27/2016 | Transfer | EF1 | Correct Below | | in break room kitchen | all 120V 15-20 amp recetpacle must be GFI protected and readily accessible |
| 1/27/2016 | Transfer | EF1 | Correct Below | | at water heater disconnect | bond around knockouts in disconnect |
| 1/27/2016 | Transfer | EF1 | Correct Below | | several exam rooms | receptacles within 6' of sinks must be GFI protected |
| 1/27/2016 | Transfer | EF1 | Correct Below | | in sink in room off of nurses station room 218 | all receptacles within 6' of sink must be GFI protected |