Inspection #: 385293
Inspection Type: Gas Piping
Inspector: H8
Result: Partial
Comment: Underground gas line from meter to new generator rough-in and test Approved. NOTE:1) provide plans on next inspection. NOTE:2) green tag not issued appliance not vented. NOTE:3) install approved outdoor flexes at each gas line connection. Per the 2009 UPC Sections 313.0, 315.0, and MOA amendment to the 2009 UPC, section 315.4, ‘…..use clean fill.