Inspection #: 385292
Inspection Type: Gas Piping
Inspector: R.Larson
Result: Approved
Comment: Exhaust piping from generator through roof of conex > Inspected and Approved. NOTES: 1) To obtain gas green tag, all gas piping needs to be completed, tested, and inspected. This would include from meter to ground piping and from ground, through conex to engine. 2) Gas piping to be tested on a gauge that has 1/10th (one tenth) pound increments or less (IFGC/MOA 406.4.1). If you do not have this gauge, Enstar has a loaner program. 3) Contractor to install ‘Dormont’ type flex connectors at meter and home connections with a minimum of 6” deflection in all directions as required by code. ( IFGC/MOA 404.18 ) > At all points where fuel gas piping enters or leaves the ground, there shall be installed, above ground, an approved/listed fuel gas connector, capable of obsorbing a 6" displacement, in any direction, due to frost heave action. NOTE: Dormont approved/listed for outdoor use. 4) Enstar 'may' require bollard protection for meter.