Inspection #: 383481
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: Please call to meet, thanks, KH Requested by: Kevin Hunter 272-3006 ||

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/12/2015 EF1Correct Below Dipping station.GFCI device must be readilly accessible (breaker).
11/12/2015 EF1Correct Below Meter / service disconnect.Label as Suite C.
11/12/2015 EF1Correct Below Stacked cookie ovens.Only(1) can be opperated on the 200A service. Remove (1) oven or provide electrical connection to both using transfer switch to ensure that both cannot opperate at one time. Cannot install electrical equipment that is not hooked up.