| Date | Status | Code | Description | Ref | Location | Comments |
| 10/15/2015 | | EF1 | Correct Below | | Feeder wire under trailer. | Needs coreflow protection from where emerging from the ground to the pipe chase up to the panel. |
| 10/15/2015 | | EF1 | Correct Below | | Panel | 3-wire feeder without EGC needs #6 CU bond between ground and neutral. |
| 10/15/2015 | | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | Under trailer feeder splice. | Show product packaging / instructions. Need to see suitability for direct burial. |
| 10/15/2015 | | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | Under trailer | Ground wire (GEC) from panel to water line needs to be: *Connected within 5 ft of where pipe emerges from the ground. *#6 copper wire. *Unbroken / unspliced from panel to water line clamp. |
| 10/15/2015 | | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | Under trailer. | Needs #6 copper gas line bond wire to panel. |
| 10/15/2015 | | ElecRoughOther | 000 Electrical Rough Other | Please correct the following: | Front of trailer near parking area. | Need headbolt heater outlet. Needs the following: *Dedicated circuit. *GFCI protection. Type TR / WR receptacle. *Weatherproof box with''in-use cover''. |