Click Here To View Another Inspection


Inspection #: 378836
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Approved
Comment: Call Requested by: John pardue 9078419088 jpardue@chenga.com ||

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/30/2015 EF1Correct Below at panelspanel labeling must incude feeder disconnect location
9/30/2015 EF1Correct Below in room R145output circuit from inverter is an emergency circuit and must be in separate conduits/j-boxes
9/30/2015 EF1Correct Below at dust collectordisconnect required within sight of controller, label disconnects at motors, need to verfy motor ratings/overloads
9/30/2015 EF1Correct Below kitchen roomone GFR bad in center of window, GFI behind washer not readily accessible
9/30/2015 EF1Correct Below in hallwayneed to verify em lighting in hallway