| Date | Status | Code | Description | Ref | Location | Comments |
| 9/30/2015 | | EF1 | Correct Below | | at panels | panel labeling must incude feeder disconnect location |
| 9/30/2015 | | EF1 | Correct Below | | in room R145 | output circuit from inverter is an emergency circuit and must be in separate conduits/j-boxes |
| 9/30/2015 | | EF1 | Correct Below | | at dust collector | disconnect required within sight of controller, label disconnects at motors, need to verfy motor ratings/overloads |
| 9/30/2015 | | EF1 | Correct Below | | kitchen room | one GFR bad in center of window, GFI behind washer not readily accessible |