Inspection #: 378366
Inspection Type: Final Electrical
Inspector: H8
Result: Partial
Comment: Tag #31943. Luke 631-2655.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/15/2015TransferEF1Correct Below Feeder wire under trailer.Needs coreflow protection from where emerging from the ground to the pipe chase up to the panel.
10/15/2015TransferEF1Correct Below Panel3-wire feeder without EGC needs #6 CU bond between ground and neutral.
10/15/2015TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:Under trailer feeder splice.Show product packaging / instructions. Need to see suitability for direct burial.
10/15/2015TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:Under trailerGround wire (GEC) from panel to water line needs to be: *Connected within 5 ft of where pipe emerges from the ground. *#6 copper wire. *Unbroken / unspliced from panel to water line clamp.
10/15/2015TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:Under trailer.Needs #6 copper gas line bond wire to panel.
10/15/2015TransferElecRoughOther000 Electrical Rough OtherPlease correct the following:Front of trailer near parking area.Need headbolt heater outlet. Needs the following: *Dedicated circuit. *GFCI protection. Type TR / WR receptacle. *Weatherproof box with''in-use cover''.