Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 377252
Inspection Type: Final Electrical
Inspector: D.Rooney
Result: Approved
Comment: Please call before heading over Requested by: Ralph Pate 909-297-8505 ||

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/11/2015 EF1Correct Below StoreH&M store management needs to be able to produce a key and demonstrate access to main breaker serving the store.
12/11/2015 EF1Correct Below Main store disconnect.Mall management must provide a letter to building safety stating: 1. That H&M management will have a key to the room. 2. The procedure for getting the elevator to the lower level and getting buzzed past the security gate by security. 3. That security staff are available to buzz people through the gate 24/7.
9/15/2015 EF1Correct Below South end gutter with more than 30 conductors in a cross section.#10 wire for multi receptacle circuits cannot be on larger than 15A breakers. #12 wires cannot be on 15A breakers becauseof derating.
9/15/2015 EF1Correct Below North gutter with more than 30 conductors in cross section.Multi receptacle circuits on #10 wire from pnl LP-2 need 15A OCPD toi meet derating requirements.
9/15/2015 EF1Correct Below Lighting controllers beneeth duct. (do not have 6 ft dedicated space above)1.Put out (2) 1'' conduits to boxes at front of duct for future access. 2. Drip protection above controllers.
7/14/2015 EF1Correct Below Panel schedulesMake breaker designations unique, specific.
7/14/2015 EF1Correct Below Janitor's closetBond around watewr meter.
7/14/2015 EF1Correct Below Various sales areasSeveral cable hung lights not installed.
7/14/2015 EF1Correct Below Various sales areas.Several reccessed EM lights missing bulbs. AFD has given fire CCO.Will need to re-checK EM lights.
7/14/2015 EF1Correct Below Electrical room.Gutters have more than 30 conductors in cross sectional area.
7/14/2015 EF1Correct Below PanelsNeed labelling as to source of supply.
7/8/2015 EF1Correct Below Both entrances to Kid's Dept.Missing EM fixtures.
7/8/2015 EF1Correct Below Lan roomMissing light fiture.
7/8/2015 EF1Correct Below Stock room occupancy sensorsSepparate class 1 from class 2 wiring. Boxes need seismic wire.
7/8/2015 EF1Correct Below Back of store.Exit signsnot coming on.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter