Date | Status | Code | Description | Ref | Location | Comments |
12/11/2015 | | EF1 | Correct Below | | Store | H&M store management needs to be able to produce a key and demonstrate access to main breaker serving the store. |
12/11/2015 | | EF1 | Correct Below | | Main store disconnect. | Mall management must provide a letter to building safety stating: 1. That H&M management will have a key to the room. 2. The procedure for getting the elevator to the lower level and getting buzzed past the security gate by security. 3. That security staff are available to buzz people through the gate 24/7. |
9/15/2015 | | EF1 | Correct Below | | South end gutter with more than 30 conductors in a cross section. | #10 wire for multi receptacle circuits cannot be on larger than 15A breakers. #12 wires cannot be on 15A breakers becauseof derating. |
9/15/2015 | | EF1 | Correct Below | | North gutter with more than 30 conductors in cross section. | Multi receptacle circuits on #10 wire from pnl LP-2 need 15A OCPD toi meet derating requirements. |
9/15/2015 | | EF1 | Correct Below | | Lighting controllers beneeth duct. (do not have 6 ft dedicated space above) | 1.Put out (2) 1'' conduits to boxes at front of duct for future access. 2. Drip protection above controllers. |
7/14/2015 | | EF1 | Correct Below | | Panel schedules | Make breaker designations unique, specific. |
7/14/2015 | | EF1 | Correct Below | | Janitor's closet | Bond around watewr meter. |
7/14/2015 | | EF1 | Correct Below | | Various sales areas | Several cable hung lights not installed. |
7/14/2015 | | EF1 | Correct Below | | Various sales areas. | Several reccessed EM lights missing bulbs. AFD has given fire CCO.Will need to re-checK EM lights. |
7/14/2015 | | EF1 | Correct Below | | Electrical room. | Gutters have more than 30 conductors in cross sectional area. |
7/14/2015 | | EF1 | Correct Below | | Panels | Need labelling as to source of supply. |
7/8/2015 | | EF1 | Correct Below | | Both entrances to Kid's Dept. | Missing EM fixtures. |
7/8/2015 | | EF1 | Correct Below | | Lan room | Missing light fiture. |
7/8/2015 | | EF1 | Correct Below | | Stock room occupancy sensors | Sepparate class 1 from class 2 wiring. Boxes need seismic wire. |
7/8/2015 | | EF1 | Correct Below | | Back of store. | Exit signsnot coming on. |