Inspection Type: Final Electrical
Inspector: H8
Result: Correction
Comment: Please call before coming so we can meet you there Requested by: Ray 4444399 aaeaat@acsalaska.net ||

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/15/2015TransferEF1Correct Below South end gutter with more than 30 conductors in a cross section.#10 wire for multi receptacle circuits cannot be on larger than 15A breakers. #12 wires cannot be on 15A breakers becauseof derating.
9/15/2015TransferEF1Correct Below Lighting controllers beneeth duct. (do not have 6 ft dedicated space above)1.Put out (2) 1'' conduits to boxes at front of duct for future access. 2. Drip protection above controllers.
9/15/2015TransferEF1Correct Below North gutter with more than 30 conductors in cross section.Multi receptacle circuits on #10 wire from pnl LP-2 need 15A OCPD toi meet derating requirements.
7/14/2015TransferEF1Correct Below Panel schedulesMake breaker designations unique, specific.
7/14/2015TransferEF1Correct Below PanelsNeed labelling as to source of supply.
7/14/2015TransferEF1Correct Below Electrical room.Gutters have more than 30 conductors in cross sectional area.
7/14/2015TransferEF1Correct Below Various sales areas.Several reccessed EM lights missing bulbs. AFD has given fire CCO.Will need to re-checK EM lights.
7/14/2015TransferEF1Correct Below Various sales areasSeveral cable hung lights not installed.
7/14/2015TransferEF1Correct Below Janitor's closetBond around watewr meter.
7/8/2015TransferEF1Correct Below Lan roomMissing light fiture.
7/8/2015TransferEF1Correct Below Stock room occupancy sensorsSepparate class 1 from class 2 wiring. Boxes need seismic wire.
7/8/2015TransferEF1Correct Below Back of store.Exit signsnot coming on.
7/8/2015TransferEF1Correct Below Both entrances to Kid's Dept.Missing EM fixtures.