Inspection #: 374965
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: call hamza Requested by: hamza 222-4000 info@progressiveak.com ||

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/1/2015 EF1Correct Below SE corner exit.Blank plate at unused exit sign box.
9/1/2015 EF1Correct Below Sales floor lighting.Portable cord fed strip lights: 1. Cords cannot be concealed by or located above a suspended or dropped ceiling per NEC 400.8(5). 2.Fixtures listed as portable luminaires. Are these allowed for permanent mounting? 3. Per 8/14/2015 inspection, is the special receptacle box which interfaces with building wiring covered by the fixture listing? No UL or UR mark.
9/1/2015 EF1Correct Below Sales floor ceiling.LED driver for sign needs disconnect.
9/1/2015 EF1Correct Below Shampoo sinksGFCI receptacle not tripping when tested.
9/1/2015 EF1Correct Below Product display shelves.Cords cannot be pinched by shelving.
9/1/2015 EF1Correct Below Sales floor light boxes, cabinetry.Verify that cord ends can fit through holes.
9/1/2015 EF1Correct Below PanelsPost source of supply.
9/1/2015 EF1Correct Below Panel schedulesCircuit designations need to be specific, unique.
9/1/2015 EF1Correct Below Under cabinet refrigerator.Receptacle within 6ft of sink needs GFCI protection.