Date | Status | Code | Description | Ref | Location | Comments |
9/1/2015 | | EF1 | Correct Below | | SE corner exit. | Blank plate at unused exit sign box. |
9/1/2015 | | EF1 | Correct Below | | Sales floor lighting. | Portable cord fed strip lights: 1. Cords cannot be concealed by or located above a suspended or dropped ceiling per NEC 400.8(5). 2.Fixtures listed as portable luminaires. Are these allowed for permanent mounting? 3. Per 8/14/2015 inspection, is the special receptacle box which interfaces with building wiring covered by the fixture listing? No UL or UR mark. |
9/1/2015 | | EF1 | Correct Below | | Sales floor ceiling. | LED driver for sign needs disconnect. |
9/1/2015 | | EF1 | Correct Below | | Shampoo sinks | GFCI receptacle not tripping when tested. |
9/1/2015 | | EF1 | Correct Below | | Product display shelves. | Cords cannot be pinched by shelving. |
9/1/2015 | | EF1 | Correct Below | | Sales floor light boxes, cabinetry. | Verify that cord ends can fit through holes. |
9/1/2015 | | EF1 | Correct Below | | Panels | Post source of supply. |
9/1/2015 | | EF1 | Correct Below | | Panel schedules | Circuit designations need to be specific, unique. |
9/1/2015 | | EF1 | Correct Below | | Under cabinet refrigerator. | Receptacle within 6ft of sink needs GFCI protection. |