Inspection #: 368179
Inspection Type: Final Electrical
Inspector: H8
Result: Cancel
Comment: Request for CCO extension for Corrections received on report dated 7/14/15 to be extended to 9/11/15 to correct all items on inspection report. We are still working on getting some material onsite. Requested by: Erik Guerrero 9099490380 eguerrero@timberwolff.com ||

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/14/2015TransferEF1Correct Below Panel schedulesMake breaker designations unique, specific.
7/14/2015TransferEF1Correct Below Janitor's closetBond around watewr meter.
7/14/2015TransferEF1Correct Below Various sales areasSeveral cable hung lights not installed.
7/14/2015TransferEF1Correct Below Various sales areas.Several reccessed EM lights missing bulbs. AFD has given fire CCO.Will need to re-checK EM lights.
7/14/2015TransferEF1Correct Below Electrical room.Gutters have more than 30 conductors in cross sectional area.
7/14/2015TransferEF1Correct Below PanelsNeed labelling as to source of supply.
7/8/2015TransferEF1Correct Below Both entrances to Kid's Dept.Missing EM fixtures.
7/8/2015TransferEF1Correct Below Stock room occupancy sensorsSepparate class 1 from class 2 wiring. Boxes need seismic wire.
7/8/2015TransferEF1Correct Below Back of store.Exit signsnot coming on.
7/8/2015TransferEF1Correct Below Lan roomMissing light fiture.