Date | Status | Code | Description | Ref | Location | Comments |
7/14/2015 | Transfer | EF1 | Correct Below | | Panel schedules | Make breaker designations unique, specific. |
7/14/2015 | Transfer | EF1 | Correct Below | | Janitor's closet | Bond around watewr meter. |
7/14/2015 | Transfer | EF1 | Correct Below | | Various sales areas | Several cable hung lights not installed. |
7/14/2015 | Transfer | EF1 | Correct Below | | Various sales areas. | Several reccessed EM lights missing bulbs. AFD has given fire CCO.Will need to re-checK EM lights. |
7/14/2015 | Transfer | EF1 | Correct Below | | Electrical room. | Gutters have more than 30 conductors in cross sectional area. |
7/14/2015 | Transfer | EF1 | Correct Below | | Panels | Need labelling as to source of supply. |
7/8/2015 | Transfer | EF1 | Correct Below | | Both entrances to Kid's Dept. | Missing EM fixtures. |
7/8/2015 | Transfer | EF1 | Correct Below | | Stock room occupancy sensors | Sepparate class 1 from class 2 wiring. Boxes need seismic wire. |
7/8/2015 | Transfer | EF1 | Correct Below | | Back of store. | Exit signsnot coming on. |
7/8/2015 | Transfer | EF1 | Correct Below | | Lan room | Missing light fiture. |