Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 366654
Inspection Type: Final Electrical
Inspector: H8
Result: Partial
Comment: Conditional electrical final extended until 8/15/2015 to correct items noted at 7/14/2015 inspection.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/14/2015TransferEF1Correct Below Panel schedulesMake breaker designations unique, specific.
7/14/2015TransferEF1Correct Below Janitor's closetBond around watewr meter.
7/14/2015TransferEF1Correct Below Various sales areasSeveral cable hung lights not installed.
7/14/2015TransferEF1Correct Below Various sales areas.Several reccessed EM lights missing bulbs. AFD has given fire CCO.Will need to re-checK EM lights.
7/14/2015TransferEF1Correct Below Electrical room.Gutters have more than 30 conductors in cross sectional area.
7/14/2015TransferEF1Correct Below PanelsNeed labelling as to source of supply.
7/8/2015TransferEF1Correct Below Both entrances to Kid's Dept.Missing EM fixtures.
7/8/2015TransferEF1Correct Below Lan roomMissing light fiture.
7/8/2015TransferEF1Correct Below Stock room occupancy sensorsSepparate class 1 from class 2 wiring. Boxes need seismic wire.
7/8/2015TransferEF1Correct Below Back of store.Exit signsnot coming on.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter