Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 359567
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: Ulta Beauty core and shell. Contractor completing bonding around water meters.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/9/2015 EF1Correct Below Rooftop.RTUs, EFs not installed.
6/9/2015 EF1Correct Below 112.5 KVA XFMR.XFMRs larger than 50 KVA cannot be mounted above a ceiling.
6/9/2015 EF1Correct Below XFMR at power distribution center.Bond to water line in area served.
6/9/2015 EF1Correct Below Sprinkler roomInstall light, switch receptacle, etc. Reconnect existing GEC to water line.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS