Inspection #: 356893
Inspection Type: Ceiling / Act
Inspector: J.Stubbs
Result: Approved
Comment: Grid ceiling framing inspected & approved .

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/21/2015 ACTBACT CorrectionComplete the following corrections : PROVIDE WIRES TO SUPPORT MAINS 4 FT OC MAX
5/21/2015 ACTBACT CorrectionComplete the following corrections : WIRES TO BE TIED WITH 3 COMPLETE TWISTS WITHIN 3 INCHES
5/21/2015 ACTBACT CorrectionComplete the following corrections : WIRES SHALL NOT EXCEED I INCH AND 6 INCHES OUT OF PLUMB.
5/21/2015 ACTBACT CorrectionComplete the following corrections : PROVIDE SUPPORT WIRES ON ALL TEES LONGER THAN 8 INCHES