Inspection #: 356585
Inspection Type: Final Electrical
Inspector: H8
Result: Partial
Comment: electrical final for phase 1 emergency department only approved *canopy area remains for phase 1 Correction: Correct Below Note: 15A max ocp at rtu recep Correction: Correct Below Note: label em receps Correction: Correct Below Note: clarify panel schedules Correction: Correct Below Note: bond panelboards serving patient care areas

Inspection Corrections