Inspection #: 356396
Inspection Type: Ceiling / Act
Inspector: H8
Result: Correction
Comment: NOT READY Correction: ACT Correction Note: PROVIDE SUPPORT WIRES ON ALL TEES LONGER THAN 8 INCHES Correction: ACT Correction Note: PROVIDE WIRES TO SUPPORT MAINS 4 FT OC MAX Correction: ACT Correction Note: WIRES TO BE TIED WITH 3 COMPLETE TWISTS WITHIN 3 INCHES Correction: ACT Correction Note: WIRES SHALL NOT EXCEED I INCH AND 6 INCHES OUT OF PLUMB.